Commissioning

Your modules are wired (Hardware Guide) and the firmware is flashed (Compilation). This guide binds the modules to roles and starts regulation.

A v2.0 system is a host MCU plus external smart modules — rbAmp (sensing) and DimmerLink (dimmers) — on the I2C bus. The UI is external (the device serves GET / → 302), so you drive commissioning either through the external web app pointed at the device's IP, or with the REST API directly.

Profile note. The REST commissioning flow below is available on the ESP32 and C2-HTTP builds. C2-MQTT is headless — it has no REST API; commission it over MQTT (MQTT-bootstrap, see the MQTT Guide).

The bring-up path: WiFi → discover → assign roles → CT model → verify grid sign → start AUTO.

The bring-up path: WiFi → discover → assign roles → CT model → verify grid sign → start AUTO.

Connect to WiFi first

Steps 1–7 are done through the web app or REST, so get the device onto your network first:

  1. On first boot the device starts its own WiFi access point — SSID ACRouter_XXXX. Join it from a phone/laptop and open http://192.168.4.1.
  2. Give it your home WiFi (in the web app, or POST /api/wifi/connect {"ssid":"…","password":"…"}, or the serial wifi-connect <ssid> <password> command). It saves the credentials and joins your LAN.
  3. Find its new IP with GET /api/wifi/status (or the wifi-status serial command), and use that IP for the rest of the steps.

No WiFi? Use serial instead. Every step below has a serial-console equivalent (115200 8N1) — you can commission the device entirely over USB without WiFi (see Terminal Commands). Step 0 (I2C bus pins) is always available over serial.


Key Principles

  • Roles are per-channel, not per-module. A module is a device (an address); a role is attached to an (address, channel) pair. The registry (GET /api/modules) is the source of truth.
  • The grid role must be on a module that also measures voltage. Only a channel with a voltage reference produces signed power (import vs. export). A current-only (CT-only) channel cannot tell direction. You can tell which modules are voltage-capable from has_voltage: true in GET /api/rbamp/modules (this flag is not in GET /api/modules). Minimum viable config = one voltage-capable rbAmp as grid + one DimmerLink (without a dimmer there is nothing to regulate).
  • role = dimmer auto-binds a DimmerLink to the first free dimmer output (id 4 for the first DimmerLink, 5 for the second, …) — and it's usually auto-assigned at discovery. You work with roles and addresses, never raw output ids.
  • The voltage role is optional and distinct from has_voltage. has_voltage is a module's hardware ability to measure voltage; the voltage role designates a module as the shared voltage/frequency reference for the merge. You only assign a separate voltage module when you want the reference to come from a dedicated module — a single voltage-capable rbAmp as grid already provides it.

Step 0 — I2C Bus (only if not on default pins)

Default pins per target: ESP32 SDA 21 / SCL 22, ESP32-C2 SDA 5 / SCL 6. To change them:

plaintext
POST /api/hardware/config
{"i2c":{"bus0":{"sda":N,"scl":M}}}

This is saved to NVS and requires a reboot — the bus reads its pins at boot. After the reboot the bus can see the modules.


Step 1 — Discover (rescan)

After a rescan, the Modules page lists the discovered rbAmp and DimmerLink with their addresses and roles.

After a rescan, the Modules page lists the discovered rbAmp and DimmerLink with their addresses and roles.

plaintext
POST /api/modules/rescan        → 202 {"scanning":true}

The ~2.5 s scan runs in the background (a second rescan while busy → 409 {"error":"busy"}). Poll GET /api/modules until "scanning": false — the list is then fresh. Each module reports its family (a current DimmerLink shows as DimmerLink(legacy); rbAmp shows as rbAmp), addr, channels, current roles[], and valid_roles[] (the only roles allowed for that family — a UI offers exactly these).


Step 2 — Assign Roles (per channel)

Roles are assigned per channel on the Sensors tab — start with grid on a voltage-capable rbAmp.

Roles are assigned per channel on the Sensors tab — start with grid on a voltage-capable rbAmp.

plaintext
POST /api/modules/role
{ "addr": "0x51", "channel": 0, "role": "grid" }
  • rolegrid | solar | load | voltage | dimmer | relay | none
  • 200 {"success":true,"message":"Role saved"} · no module → 404 · bad channel → 400
  • This is the recommended way to bind a module — the registry is the source of truth, and role = dimmer auto-binds the DimmerLink to dimmer id 4.

Start with the mandatory grid channel (on a voltage-capable rbAmp), then add solar / load as wired, and dimmer for the DimmerLink.

🔁 Assigning role=dimmer binds and drives the output live — no reboot is needed for the dimmer to actuate the load. A one-time reboot may be needed for the dimmer's status/telemetry to populate (the status poll task is created at boot when ≥1 dimmer is enabled). Subsequent dimmers and level changes apply live.


Step 3 — Set the CT Model (per rbAmp channel)

Select the CT model matching your clamp — this overwrites the factory gain, so set it once.

Select the CT model matching your clamp — this overwrites the factory gain, so set it once.

Fetch the catalog with GET /api/rbamp/ct-models, then set the model that matches your physical CT:

plaintext
POST /api/rbamp/modules/ct-model
{ "addr": "0x51", "ct_model": "sct013-030" }        → 202 {"pending":true, …}
  • ct_model is a catalog id (e.g. sct013-030 = a 30 A clamp).
  • ⚠️ Changing the CT model overwrites the module's per-unit factory gain calibration with the model's preset gain. Set it once for the correct clamp; re-selecting the same model is a no-op.

Step 4 — Resolve Address Conflicts (re-address)

If two modules share the same default address, give each a unique one:

plaintext
POST /api/rbamp/modules/address
{ "addr": "0x51", "new_addr": "0x52" }              → 202 {"pending":true, …}

Two-phase commit; the new address applies after the module resets. Run a rescan afterwards — the module re-appears at the new address and its role mapping migrates automatically.

🔴 Address two same-address modules one at a time. Two modules at the same factory address both answer on it, so you can't target one to re-address it. Connect them to the bus one at a time for the initial re-addressing, then bring the rest online.


Step 5 — Name the Channels (optional)

POST /api/modules/name sets a human-readable per-channel name that shows up in GET /api/modules (names[]) and the UI.


Step 6 — Verify Sensing

Confirm the grid direction under a known load — it must read 'Importing from grid' — before you enable AUTO.

Confirm the grid direction under a known load — it must read 'Importing from grid' — before you enable AUTO.

Read GET /api/sensors (per-source live V/I/P/PF/frequency + role) or GET /api/metrics (merged power_grid / power_solar / power_load).

🔴 Check the grid sign under a known load. power_grid must read + when importing and when exporting. If the sign or direction is wrong, the grid channel isn't voltage-capable, or the CT model / clamp polarity is off.


Step 7 — Start a Mode

plaintext
POST /api/mode
{ "mode": "auto" }

Modes: off · auto · eco · offgrid · manual · boost · grid_limit. For grid_limit, set the current cap: POST /api/config {"grid_current_limit": <A>} (default 16.0 A). See Router Modes for what each mode does.

Your system is now regulating — in AUTO it will raise the dimmer whenever you'd otherwise export, so the surplus heats your load instead of feeding the grid.


Troubleshooting

Symptom Check
i2c-scan / rescan finds nothing Module power (3V3) and common ground; the two 4.7 kΩ pull-ups on SDA/SCL; correct bus pins for your target (Hardware Guide §1.2); on a C2, that you didn't reuse a strapping/flash pin.
Dimmer assigned but the load doesn't move Did you reboot once after enabling the first DimmerLink? (Step 2 note.) Is the mode AUTO/BOOST/MANUAL and is there surplus to divert?
power_grid sign is inverted (+/− swapped) Flip the grid CT clamp around the conductor (the clamp has an arrow for current direction). A wrong sign is dangerous in AUTO — fix it before enabling AUTO.
power_grid reads 0 / unstable The grid module must be voltage-capable (has_voltage:true in /api/rbamp/modules); the CT must clamp a single conductor (L and N together read ≈0).
Serial console / COM port not visible Install the USB-UART driver for your board (CP210x or CH340); on Linux add your user to the dialout group.
Two modules won't address They share a factory address and both answer — connect them one at a time to re-address (Step 4).

Not in v2.0

If you followed a v1.x commissioning guide, these steps are gone (sensing moved to smart modules):

  • ADC channel setup (adc_channels) — ignored; sensing is external.
  • Sensor-driver selection/api/hardware/sensor-profiles, /sensor-types, /voltage-drivers, /current-drivers are removed (smart modules are factory-calibrated).
  • Per-GPIO dimmer config (/api/dimmers/{0-3}/…) — removed; the dimmer is driven by the router mode, not per channel.

ESP-NOW nodes (ESP32 only). On an ESP32 build, wireless measurement nodes appear with source: espnow, are keyed by MAC, and their dimmer outputs start at id 12+. Assign their roles with POST /api/espnow/nodes {"mac":…,"role":…} (or serial espnow-config) — /api/modules/role takes an I2C address, not a MAC. ESP-NOW is an ESP32-tier feature; the ESP32-C2 uses wired DimmerLink over I2C.